| High Voltage Insulation Tapes |
| TS-1 SELF AMALGAMATING EPDM
HIGH VOLTAGE TAPE |
| |
| PROPERTIES OF TS-1 TAPES
Physical : as per ASTM D-4325 tested and certified
by CPRI, Bangalore & NTH, Mumbai
|
| Colour |
Black |
| Thickness |
0.75 MM |
| Tensile |
9-10 kg/cm2 |
| Elongation at Break |
350-400 % Min. |
| Amalgamation |
Very Good |
| Heat Resistance at 900C |
Very Good |
| Operating Temperature |
900C continuous |
| Emergency Overload |
1300C |
| Water Resistance |
Very Good |
| Moisture Absorption |
Max 0.04% |
|
| |
|
Chemical : as per ASTM D-4325 tested and certified
by CPRI Bangalore & NTH, Mumbai
|
| Resistance to Acid, Alkali |
Good |
| Ozone Resistance |
Excellent |
| UV Resistance |
Good |
| Oil, Grease, Solvents, Petrol |
Attacked |
|
| |
|
Electrical : as per ASTM D-4325 tested and certified
by CPRI Bangalore & NTH, Mumbai
|
| Volume |
1 x 1015 ohm-cm (270C) |
| Dissipation Factor at 50 Hz |
0.007 |
Dissipation Factor @ 230C
in
distilled water |
0.007 |
| Dielectric constant |
3 |
| Dielectric Factor @ 700C in
distilled water for 16 mm |
0.007 |
| Dielectric constant |
3 |
Dielectric Strength
(after standard conditioning) |
29 kV / mm |
| After 96 hrs at 96% RH |
>90% of Std Condition Value |
Insulation Resistance
(Indirect method of electrolytic corrosion)
|
>1 x 106 megohms |
Dielectric Strength at
elevated temperature
|
@ 1300C Dielectric Strength
>90% of Std
Value and no blistering / cracking |
|
| |
| APPLICATIONS |
 |
Cable Jointing : Primary insulation and
jacketing can be done using TS-1 tape very easily in making
straight through joints and bifurcated joints. The void-free
insulation yields moisture proof jacketing. |
 |
Cable Termination : TS-1 tape can be used
to terminate cables and is recommended in building stress
cones. |
 |
Insulating Busbar : At present busbars
in control panels are being insulated by adhesive H.T.
Tapes, which last for hardly 6-8 months, Moreover since
adhesive H.T. Tapes do not provide adequate protection
from moisture such innovative but highly dangerous methods
like using electric heaters below these joints are being
used. To prevent moisture from seeping in specially during
monsoons, TS-1 HV Tapes provide total moisture, corrosion,
UV, Ozone and Chemical resistance for very long period
doing away with the need to replace busbar insulation
frequently. |
 |
Protection Against Bird Faults : During
nesting season and otherwise, power interruptions occur
due to bird faults which can be eliminated by sing TS-1. |
|
| |
| PRODUCT RANGE |
| a) |
a) TS-1 - Self amalgamating high voltage
EPDM tape Size 25mm x 10mt |
| b) |
a) TS-2 - PCP cable repair tape |
| c) |
a) TS-3 - Semi conductive tape |
| d) |
a) TS-5 - Silicon rubber tape |
| e) |
a) LT&HT Power cable jointing kits |
|